Branch Circuit Monitoring
NHP’s branch monitoring solution connects directly to the load side of circuit breakers for simultaneous monitoring of numerous single and/or three-phase loads. Its compact size and ability to monitor up to 96 channels with its respective split core current sensor TCD12 makes it ideal for high-density monitoring within a Power Distribution Unit (PDU).
Features and Benefits
- Compact size meter and CTs to fit in panelboards
- Easy to connect CTs scalable to monitor and analyse any combination of single-phase, two-phase, and three-phase loads for a maximum of 96 channels, up to 32A per channel
- Capability to monitor locally or remote with free to download UCS software
- Options for Modbus RTU or TCP
- View up to six different energy tariffs
- Up to 16 alarm management
WM50
Branch circuit monitoring solution
Connection type:
Connect up to 8x 12-channel CTs (TCD12)
System Variables:
kWh, kVArh, V, A, VA/W/Var, PF, Hz, THD (32nd harmonic), K-factor, phase-sequence
Active energy accuracy /IEC 62053-21:
Class 0.5S (mains), Class 2 for individual channels
Four Quadrant Monitoring:
Yes
Comms Enabled:
Yes (Ethernet TCP or Modbus RTU)
Other I/O:
Various configurations available through add-on modules, including digital I/O and analogue and temperature inputs
Additional Features:
Up to 16 internal alarms available, event and datalogging with onboard memory